- MPI-505电气安装测试仪
详细信息
品牌:sonel 加工定制:否 型号:MPI-505 外形尺寸:见说明 mm 重量:见说明 g 适用范围:见说明 用途:见说明 电源电压:见说明 V -
Measurement of short-circuit loop parameters:
- in L-PE, L-N, L-L circuits as well as in L-PE (RCD) circuits - without tripping RCD breakers of current 30 mA.
- impedance measurement of short-circuit loops in power networks of nominal voltages: 115/200 V, 220/380 V, 230/400 V, 240/415 V and frequencies in the range of 4565 Hz.. -
Testing of AC and A types residual current circuit breakers:
- testing of regular and selective residual current circuit breakers of nominal differential currents: 10 mA, 30 mA, 100 mA, 300 mA, 500 mA, 1000 mA,
- IA trip current measurement,
- tA trip time measurement for 0.5In, In, 2In, 5In,
- measurement of earth continuity and touch voltage without tripping RCDs,
- functionality of automatic measurement of residual current circuit breaker parameters. - Measurement of insulation resistance at voltages: 100 V, 250 V, 500 V and 1000 V.
-
Low-voltage measurement of resistance, protective connections and equipotential bonding:
- measurement of continuity of protective connections with current ±200 mA,
- automatic calibration of test leads - capability of using any test leads,
- measurement of resistance with low current and acoustic signaling. - Quick verification of correctness of the PE wire connection with a touch probe.
- Measurement of AC voltage.
- Indication of phase sequence.
- Memory of 990 measurements, data transfer to a PC over the USB interface.
MPI-505 is equipment to perform complete test and verify on electrical installations according to the most common safety standards (IEC 61557, VDE 0100, BS7671).
MPI-505电气安装测试仪技术参数:
Measurement of short-circuit loop impedance ZL-PE, ZL-N, ZL-L
Measurement range acc. to IEC 61557: 0.13...1999Ω for a 1.2 m test lead:
Display range Resolution Accuracy 0,00...19,99Ω 0,01Ω ±(5% m.v +5 digits) 20,0...199,9Ω 0,1Ω 200...1999Ω 1Ω • Nominal operating voltage UnL-N/ UnL-L: 115/200V, 220/380V, 230/400V, 240/415V
• Operating voltage range: 100…264V (for ZL-PE i ZL-N) and 100…440V (for ZL-L)
• Nominal power network frequency fn: 50Hz, 60Hz
• Operating frequency range: 45…65Hz
• Maximal measurement current: 23A at 230V (10ms), 40A at 400V (10ms),
• Verification of correctness of the PE terminal connection with a touch (for ZL-PE)
Measurement of short-circuit loop impedance ZL-PE in the RCD mode
Measurement range acc. to IEC 61557: 0.5...1999Ω for a 1.2 m test leadDisplay range Resolution Accuracy 0,00...19,99Ω 0,01Ω ±(6% m.v + 10 digits) 20,0...199,9Ω 0,1Ω ±(6% m.v + 5 digits) 200...1999Ω 1Ω • Does not trip RCD breakers of RCD current IΔn ≥ 30mA
• Nominal operating voltage Un: 115V, 220V, 230V, 240V
• Operating voltage range: 100…264V
• Nominal power network frequency fn: 50Hz, 60Hz
• Operating frequency range: 45…65Hz
• Verification of correctness of the PE terminal connection with a touch probeMeasurement of insulation resistance
Measurement range acc. to IEC 61557-2:
• for UN = 100V: 100kΩ...500MΩ
• for UN = 250V: 250kΩ...1GΩ
• for UN = 500V: 500kΩ...2GΩ
• for UN = 1000V: 1MΩ...3GΩDisplay range*) Resolution Accuracy 0...1999kΩ 1kΩ
±(3% m.v. + 8 digits)2,00...19,99MΩ 0,01MΩ 20,0...199,9MΩ 0,1MΩ 200...500MΩ 1MΩ 200...1000MΩ 1MΩ 200...1999MΩ 1MΩ 2,00...3,00GΩ 0,01GΩ ±(4% m.v. + 6 digits) *) not exceeding the measurement range for a given voltage.
• Measurement voltage: 100 V, 250 V, 500 V and 1000 V
• Detection of presence of voltage before the measurement
• Discharge of the measured object after the measurement
• Measurements of voltage on terminals +RISO, -RISO within the range of: 0…440 V
• Measurement current < 2 mA
Low-voltage measurement of circuit continuity and resistance
Measurement of protective conductor continuity with current ±200 mA
Measurement range acc. to IEC 61557-4: 0.12...400ΩRange Resolution Accuracy 0,00...19,99Ω 0,01Ω ±(2% m.v. + 3 digits) 20,0...199,9Ω 0,1Ω 200...400Ω 1Ω • Voltage on open terminals: 4…9V
• Output current at R<2Ω: min. 200mA
• Compensation of test lead resistance
• Measurements for both polarities of currentMeasurements of RCD breaker parameters (operating voltage range 100…264 V):
RCD tripping test and measurement of tA trip time (for the tA measurement function)RCD type Test current
multiplierRange Resolution Accuracy Standard 0,5*IΔn 0...300ms
1 ms
± (2% m.v. + 2 digits)1*IΔn 2*IΔn 0...150ms 5*IΔn 0...40ms Selective 0,5*IΔn 0...500ms 1*IΔn 2*IΔn 0...200ms 5*IΔn 0...150ms *for IΔn= 10mA and 0.5 IΔn uncertainty is + 2% m.v. + 3 digits
Measurement of IA RCD trip current for sinusoidal differential current:
Selected
currentMeasurement
rangeResolution Test
currentAccuracy 10mA 3,3...10,0mA 0,1mA 0,3xIΔn...1,0xIΔn ± 5% IΔn 30mA 9,0...30,0mA 100mA 33...100mA 1mA 300mA 90...300mA 500mA 150...500mA 1000mA 330...1000mA • Capability of starting the measurement from either positive or negative half-period of forced leakage current
Measurement of IA RCD trip current for pulsating unidirectional current:Selected
currentMeasurement
rangeResolution Test
currentAccuracy 10mA 4...20,0mA 0,1mA 0,4 x IΔn ...2,0 x IΔn ±10% IΔn 30mA 12,0...42,0mA 0,4xIΔ..1,4xIΔn 100mA 40,0...140mA 1mA 300mA 120...420mA 500mA 200...700mA • Capability of measurement for either positive or negative half-periods of forced leakage current
• Maximal time of the measurement current flow is 3200 msSonel电气安全测量仪主要型号有:
MPI-530
MPI-525
MPI-520
MPI-505
MPI-502 -
Measurement of short-circuit loop parameters:
-