• MPI-530多功能电气安装仪

    详细信息

     品牌:sonel  加工定制:否  型号:MPI-530  
     外形尺寸:见说明 mm 重量:见说明 g 适用范围:见说明  
     用途:见说明  电源电压:见说明 V  
    MPI-530多功能电气安装仪
    MPI-530多功能电气安装仪产品描述:
            MPI-530 meter is a multi-functional instrument for electric shock protection measurements including the option of various methods for measuring earthing and earthing resistance. Additionally the meter enables its user to analyse power supply parameters, records and displays them on its screen. The instrument automatically measures the insulation resistance in a socket and in 3 -, 4 - and 5-wire cables when used with AutoISO-1000C adapter. Measurement results may be continuously verified, depending on user’s demand or according to binding regulations. Memory of the instrument may store tens of thousands of measurements allowing users to store them in a structure of a protocol and describe individual measurement points.
    MPI-530多功能电气安装仪技术参数:

    Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L
    Test current: 23/40A; measuring range acc. to IEC 61557: 0,13...1999,9 Ω
    (for 1.2m test lead):

    Display range Resolution Accuracy
    0,000...19,999 Ω 0,001 Ω ±(5% m.v. + 30 digits)
    20,00...199,99 Ω 0,01 Ω
    200,0...1999,9 Ω 0,1 Ω

    Rated voltage: 95...270 V (for ZL-PE and ZL-N) and 95...440 V (for ZL-L)
    Frequency: 45...65 Hz;

    Measurement of short circuit loop impedance ZL-PE in RCD mode
    Test current: 15mA, measuring range acc. to IEC 61557: 0,50...1999 Ω

    Display range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(6% w.m. + 10 digits)
    20,0...199,9 Ω 0,1 Ω ±(6% w.m. + 5 digits)
    200...1999 Ω 1 Ω

    Rated voltage: 95...270 V
    Frequency: 45...65 Hz

    Measurement of earth resistance RE with the 3p and 4p method
    Measuring range acc. to IEC 61557-5:
    0,50 Ω…1,99 kΩ for test voltage 50 V
    0,56 Ω…1,99 kΩ for test voltage 25 V

    Display range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
    10,0...99,9 Ω 0,1 Ω ±(2% m.v.. + 3 digits)
    100...999 Ω 1 Ω
    1,00...1,99 kΩ 0,01 kΩ
    · test voltage: 25 V or 50 V rms
    · test current: 20 mA, sinusoidal rms 125 Hz (for fn=50 Hz) and 150 Hz (for fn=60 Hz)
    · measurement blocked at interference voltage UN > 24 V
    · maximum measured interference voltage Unmax= 100 V
    · maximum resistance of auxiliary earth electrodes 50 kΩ

    Selective earth resistance measurement with clamp (3p + clamp)
    Measuring range acc. to IEC 61557-5: 1Ω…1,99 kΩ

    Display range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(8% m.v. + 4 digits)
    10,0...99,9 Ω 0,1 Ω
    100...999 Ω 1 Ω
    1,00...1,99 kΩ 0,01 kΩ

    · measurement with additional current clamp
    · interference current measuring range: up to 9,99 A

    Selective earth measurement with two clamps

    Display range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(10% m.v. + 4 digits)
    10,0...99,9 Ω 0,1 Ω
    100...999 Ω ±(20% m.v. + 4 digits)
    · measurement with transmitting and receiving clamps
    · interference current measuring range: up to 9,99 A

    Soil resistivity mesurement (ρ)

    Display range Resolution Accuracy
    0,0...99,9 Ωm 0,1 Ωm Depending on accuracy
    of RE measurement
    100...999 Ωm 1 Ωm
    1,00...9,99 Ωm 0,01 kΩm
    10,0...99,9 kΩm 0,1 kΩm

    · measurement with Wenner’s method
    · distance settable in metres or feet
    · distance range: 1...30 m (1...90 feet)

    Phase sequence indication

    • Phase sequence indication: conforming, non-conforming

    • Mains voltage range UL-L: 100...440 V (45...65 Hz)
    • Display of phase-to-phase voltage values

    Measurements of RCD parameters (voltage range 95...270 V):

    RCD tripping test and measurement of tripping time tA (for tA measurement function)

    RCD type Current Range Resolution Accuracy
    General and
    short-time
    delay
    0,5*IΔn 0...300 ms

    1 ms


    ± (2% m.v. + 2 digits)

    (for RCD with IΔn=10 mA
    and 0,5xIΔn uncertainty:
    ±(2% m.v. + 3 digits)

    1*IΔn
    2*IΔn 0...150 ms
    5*IΔn 0...40 ms
    Selective 0,5*IΔn 0...500 ms
    1*IΔn
    2*IΔn 0...200 ms
    5*IΔn 0...150 ms

    accuracy of residual current application: for 0,5*IΔn:-8...0% for 1*IΔn, 2*IΔn, 5*IΔn: 0...8%

    Measurement of RCD tripping current IA for sinusoidal residual current (AC type)

    Rated
    current
    Meas. range Resolution Test current Accuracy
    10 mA 3,3...10,0 mA 0,1 mA 0,3 x IΔ..1,0 x IΔ ± 5% IΔn
    30 mA 9,0...30,0 mA
    100 mA 33...100 mA 1 mA
    300 mA 90...300 mA
    500 mA 150...500 mA
    1000 mA 330...1000 mA
    The measurement can be started from positive or negative half-period of forced leakage current

    Measurement of RCD tripping current IA for unidirectional residual current and unidirectional
    with the 6 mA DC bias (type A)

    Rated
    current
    Meas. range Resolution Test current Accuracy
    10 mA 3,5...20,0 mA 0,1 mA 0,35 x IΔn..2,0 x IΔn ±10%IΔn
    30 mA 10,5...42,0 mA 0,35 x IΔn..1,4 x IΔn
    100 mA 35,0...140 mA 1 mA
    300 mA 105...420 mA
    500 mA 175...700 mA

    Measurement for positive or negative half-periods of forced leakage current

    Measurement of RCD tripping current IA for direct residual current (type B)

    Rated
    current
    Meas. range Resolution Test current Accuracy
    10 mA 2,0...20,0 mA 0,1 mA 0,4 x IΔn..2,0 x IΔn ±10%IΔn
    30 mA 6...60 mA 1 mA
    100 mA 20...200 mA
    300 mA 60...600 mA
    500 mA 100...1000 mA

    Measurement for positive or negative half-periods of forced leakage current
    IΔn - rated residual current

    Insulation resistance measurements
    Measuring range acc. to IEC 61557-2:
    - for UN = 50 V: 50 kΩ...250 MΩ
    - for UN = 100 V: 100 kΩ...500 MΩ
    - for UN = 250 V: 250 kΩ...999 MΩ
    - for UN = 500 V: 500 kΩ...2 GΩ
    - for UN = 1000 V: 1,000 MΩ...9,99 GΩ

    Display range*) Resolution Accuracy
    0...1999 kΩ 1 kΩ
    ±(3% m.v. + 8 digits)
    2,00...19,99 MΩ 0,01 MΩ
    20,0...199,9 MΩ 0,1 MΩ
    200...999 MΩ 1 MΩ
    1,00...9,99 MΩ 0,01 GΩ ±(4% m.v. + 6 digits)
    *) not greater than measuring range for given voltage

    Low-voltage measurement of resistance and circuit continuity
    Measurement of protective conductor continuity with the ±200 mA current

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
    20,0...199,9 Ω 0,1 Ω
    200...400 Ω 1 Ω
    · voltage on open terminals: 4…9 V
    · output current at R < 2 Ω: min. 200 mA
    · autocalibration of test leads
    · measurements for both current polarities

    Illuminance measurement

    Range Resolution Accuracy
    0,1...99,9 lx 0,1 lx
    ±(5% m.v. + 2 digits)
    100...999 lx 1 lx
    1,00...9,99 klx 0,01 klx
    10,0...19,9 klx 0,1 klx
    - - measurement in luxes (lx) or feet-candles (fc)

     

    ANALYSIS AND RECORDING OF SINGLE-PHASE SYSTEM

    • Voltage measurement ULN: 0...500 V
    • Frequency range of measured voltages: 45,0...65,0 Hz
    • Frequency measurement range for 50...500 V voltages: 45,0...65,0 Hz (basic uncertainty max. ± 0,1% m.v. + 1 digit)
    • cosφ measurement: 0,00...1,00 (resolution 0,01)
    • Measurement and recording in single-phase system

     

    Current measurement (True RMS)

    Clamps Range Resolution Accuracy*
    C-3, C-6 0,0...99,9 mA 0,1 mA ±(5% m.v. + 3 digits)
    100...999 mA 1 mA
    C-3,C-6
    F-1, F-2, F-3
    1,00...9,99 A 0,01 A ±(5% m.v. + 5 digits)
    (C-3, C-6)
    ±(0,1% In + 2 digits)
    (F-1, F-2, F-3)
    10,0...99,9 A 0,1 A
    100...999 A 1 A
    F-1, F-2, F-3 1,00...3,00 kA 0,01 kA

    * the accuracy of current clamps must also be taken into account

    Measurement of active power P, reactive power Q, apparent power S and cosφ

    Range
    [W], [VA], [var]
    Resolution
    [W], [VA], [var]
    Accuracy*
    0...999 1 ±(7% m.v. + 3 digits)
    1,00...9,99 k 0,01 k
    10,0...99,9 k 0,1 k ±(7% m.v. + 5 digits)
    100...999 k 1 k
    1,00...1,50 M 0,01 M
    · voltage range: 0…500V
    · current range: 0...1000A (3000A)
    · mains rated frequency fn: 50Hz, 60Hz

    Voltage harmonics measurement

    Range Resolution Nr harm. Accuracy
    0,0...500 V 0,1 (1*) V 1,2,...15 ±(5% m.v. + 3 digits)
    16,...40 ±(5% m.v. + 10 digits)

    · in addition display of h02...h40 values as percent of h01 (up to 999%)
    *) from 300V to 500V

    THD (in relation to the 1st harmonics)

        Resolution Accuracy
    THD-F voltage
    (h = 2…40)
    0,0…999,9%
    for URMS ≥ 1% Unom
     
    0,1% ±5%
    THD-F current
    (h = 2...40)
    0,0…999,9%
    for IRMS ≥ 1% Inom
    0,1% ±5%

     

    NOTE: “m.v.” means “ measured value”

    The instruments conforms to:
    EN 61010-1 (general safety requirements)
    EN 61010-031 (detailed safety requirements)
    EN 61326 (electromagnetic compatibility)
    EN 61557-10 (requirements for combined instruments)
    IEC 60364-6-61 / HD 60364-6 (measurements - verification)
    IEC 60364-4-41 / HD 60364-4-41 (measurements – protection against
    electric shock)
    EN 04700 (measurements – acceptance tests)
    EN 12464 (lighting of work places)
    DIN VDE 0100
    DIN VDE 0413
    BS 7671

    Sonel电气安全测量仪主要型号有:
    MPI-530
    MPI-525
    MPI-520
    MPI-505
    MPI-502