- MPI-530多功能电气安装仪
详细信息
品牌:sonel 加工定制:否 型号:MPI-530 外形尺寸:见说明 mm 重量:见说明 g 适用范围:见说明 用途:见说明 电源电压:见说明 V
MPI-530多功能电气安装仪产品描述:
MPI-530 meter is a multi-functional instrument for electric shock protection measurements including the option of various methods for measuring earthing and earthing resistance. Additionally the meter enables its user to analyse power supply parameters, records and displays them on its screen. The instrument automatically measures the insulation resistance in a socket and in 3 -, 4 - and 5-wire cables when used with AutoISO-1000C adapter. Measurement results may be continuously verified, depending on user’s demand or according to binding regulations. Memory of the instrument may store tens of thousands of measurements allowing users to store them in a structure of a protocol and describe individual measurement points.
MPI-530多功能电气安装仪技术参数:
Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L
Test current: 23/40A; measuring range acc. to IEC 61557: 0,13...1999,9 Ω
(for 1.2m test lead):Display range Resolution Accuracy 0,000...19,999 Ω 0,001 Ω ±(5% m.v. + 30 digits) 20,00...199,99 Ω 0,01 Ω 200,0...1999,9 Ω 0,1 Ω Rated voltage: 95...270 V (for ZL-PE and ZL-N) and 95...440 V (for ZL-L)
Frequency: 45...65 Hz;Measurement of short circuit loop impedance ZL-PE in RCD mode
Test current: 15mA, measuring range acc. to IEC 61557: 0,50...1999 ΩDisplay range Resolution Accuracy 0,00...19,99 Ω 0,01 Ω ±(6% w.m. + 10 digits) 20,0...199,9 Ω 0,1 Ω ±(6% w.m. + 5 digits) 200...1999 Ω 1 Ω Rated voltage: 95...270 V
Frequency: 45...65 HzMeasurement of earth resistance RE with the 3p and 4p method
Measuring range acc. to IEC 61557-5:
0,50 Ω…1,99 kΩ for test voltage 50 V
0,56 Ω…1,99 kΩ for test voltage 25 VDisplay range Resolution Accuracy 0,00...9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits) 10,0...99,9 Ω 0,1 Ω ±(2% m.v.. + 3 digits) 100...999 Ω 1 Ω 1,00...1,99 kΩ 0,01 kΩ
· test current: 20 mA, sinusoidal rms 125 Hz (for fn=50 Hz) and 150 Hz (for fn=60 Hz)
· measurement blocked at interference voltage UN > 24 V
· maximum measured interference voltage Unmax= 100 V
· maximum resistance of auxiliary earth electrodes 50 kΩ
Selective earth resistance measurement with clamp (3p + clamp)
Measuring range acc. to IEC 61557-5: 1Ω…1,99 kΩDisplay range Resolution Accuracy 0,00...9,99 Ω 0,01 Ω ±(8% m.v. + 4 digits) 10,0...99,9 Ω 0,1 Ω 100...999 Ω 1 Ω 1,00...1,99 kΩ 0,01 kΩ · measurement with additional current clamp
· interference current measuring range: up to 9,99 ASelective earth measurement with two clamps
Display range Resolution Accuracy 0,00...9,99 Ω 0,01 Ω ±(10% m.v. + 4 digits) 10,0...99,9 Ω 0,1 Ω 100...999 Ω ±(20% m.v. + 4 digits)
· interference current measuring range: up to 9,99 ASoil resistivity mesurement (ρ)
Display range Resolution Accuracy 0,0...99,9 Ωm 0,1 Ωm Depending on accuracy
of RE measurement100...999 Ωm 1 Ωm 1,00...9,99 Ωm 0,01 kΩm 10,0...99,9 kΩm 0,1 kΩm · measurement with Wenner’s method
· distance settable in metres or feet
· distance range: 1...30 m (1...90 feet)Phase sequence indication
- Phase sequence indication: conforming, non-conforming
- Mains voltage range UL-L: 100...440 V (45...65 Hz)
- Display of phase-to-phase voltage values
Measurements of RCD parameters (voltage range 95...270 V):
RCD tripping test and measurement of tripping time tA (for tA measurement function)
RCD type Current Range Resolution Accuracy General and
short-time
delay0,5*IΔn 0...300 ms
1 ms
± (2% m.v. + 2 digits)(for RCD with IΔn=10 mA
and 0,5xIΔn uncertainty:
±(2% m.v. + 3 digits)1*IΔn 2*IΔn 0...150 ms 5*IΔn 0...40 ms Selective 0,5*IΔn 0...500 ms 1*IΔn 2*IΔn 0...200 ms 5*IΔn 0...150 ms accuracy of residual current application: for 0,5*IΔn:-8...0% for 1*IΔn, 2*IΔn, 5*IΔn: 0...8%
Measurement of RCD tripping current IA for sinusoidal residual current (AC type)
Rated
currentMeas. range Resolution Test current Accuracy 10 mA 3,3...10,0 mA 0,1 mA 0,3 x IΔ..1,0 x IΔ ± 5% IΔn 30 mA 9,0...30,0 mA 100 mA 33...100 mA 1 mA 300 mA 90...300 mA 500 mA 150...500 mA 1000 mA 330...1000 mA
Measurement of RCD tripping current IA for unidirectional residual current and unidirectional
with the 6 mA DC bias (type A)Rated
currentMeas. range Resolution Test current Accuracy 10 mA 3,5...20,0 mA 0,1 mA 0,35 x IΔn..2,0 x IΔn ±10%IΔn 30 mA 10,5...42,0 mA 0,35 x IΔn..1,4 x IΔn 100 mA 35,0...140 mA 1 mA 300 mA 105...420 mA 500 mA 175...700 mA Measurement for positive or negative half-periods of forced leakage current
Measurement of RCD tripping current IA for direct residual current (type B)
Rated
currentMeas. range Resolution Test current Accuracy 10 mA 2,0...20,0 mA 0,1 mA 0,4 x IΔn..2,0 x IΔn ±10%IΔn 30 mA 6...60 mA 1 mA 100 mA 20...200 mA 300 mA 60...600 mA 500 mA 100...1000 mA Measurement for positive or negative half-periods of forced leakage current
IΔn - rated residual currentInsulation resistance measurements
Measuring range acc. to IEC 61557-2:
- for UN = 50 V: 50 kΩ...250 MΩ
- for UN = 100 V: 100 kΩ...500 MΩ
- for UN = 250 V: 250 kΩ...999 MΩ
- for UN = 500 V: 500 kΩ...2 GΩ
- for UN = 1000 V: 1,000 MΩ...9,99 GΩDisplay range*) Resolution Accuracy 0...1999 kΩ 1 kΩ
±(3% m.v. + 8 digits)2,00...19,99 MΩ 0,01 MΩ 20,0...199,9 MΩ 0,1 MΩ 200...999 MΩ 1 MΩ 1,00...9,99 MΩ 0,01 GΩ ±(4% m.v. + 6 digits) Low-voltage measurement of resistance and circuit continuity
Measurement of protective conductor continuity with the ±200 mA currentRange Resolution Accuracy 0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits) 20,0...199,9 Ω 0,1 Ω 200...400 Ω 1 Ω
· output current at R < 2 Ω: min. 200 mA
· autocalibration of test leads
· measurements for both current polaritiesIlluminance measurement
Range Resolution Accuracy 0,1...99,9 lx 0,1 lx
±(5% m.v. + 2 digits)100...999 lx 1 lx 1,00...9,99 klx 0,01 klx 10,0...19,9 klx 0,1 klx ANALYSIS AND RECORDING OF SINGLE-PHASE SYSTEM
- Voltage measurement ULN: 0...500 V
- Frequency range of measured voltages: 45,0...65,0 Hz
- Frequency measurement range for 50...500 V voltages: 45,0...65,0 Hz (basic uncertainty max. ± 0,1% m.v. + 1 digit)
- cosφ measurement: 0,00...1,00 (resolution 0,01)
- Measurement and recording in single-phase system
Current measurement (True RMS)
Clamps Range Resolution Accuracy* C-3, C-6 0,0...99,9 mA 0,1 mA ±(5% m.v. + 3 digits) 100...999 mA 1 mA C-3,C-6
F-1, F-2, F-31,00...9,99 A 0,01 A ±(5% m.v. + 5 digits)
(C-3, C-6)
±(0,1% In + 2 digits)
(F-1, F-2, F-3)10,0...99,9 A 0,1 A 100...999 A 1 A F-1, F-2, F-3 1,00...3,00 kA 0,01 kA * the accuracy of current clamps must also be taken into account
Measurement of active power P, reactive power Q, apparent power S and cosφ
Range
[W], [VA], [var]Resolution
[W], [VA], [var]Accuracy* 0...999 1 ±(7% m.v. + 3 digits) 1,00...9,99 k 0,01 k 10,0...99,9 k 0,1 k ±(7% m.v. + 5 digits) 100...999 k 1 k 1,00...1,50 M 0,01 M
· current range: 0...1000A (3000A)
· mains rated frequency fn: 50Hz, 60Hz
Voltage harmonics measurement
Range Resolution Nr harm. Accuracy 0,0...500 V 0,1 (1*) V 1,2,...15 ±(5% m.v. + 3 digits) 16,...40 ±(5% m.v. + 10 digits) · in addition display of h02...h40 values as percent of h01 (up to 999%)
*) from 300V to 500VTHD (in relation to the 1st harmonics)
Resolution Accuracy THD-F voltage
(h = 2…40)0,0…999,9%
for URMS ≥ 1% Unom
0,1% ±5% THD-F current
(h = 2...40)0,0…999,9%
for IRMS ≥ 1% Inom0,1% ±5% NOTE: “m.v.” means “ measured value”
The instruments conforms to:
EN 61010-1 (general safety requirements)
EN 61010-031 (detailed safety requirements)
EN 61326 (electromagnetic compatibility)
EN 61557-10 (requirements for combined instruments)
IEC 60364-6-61 / HD 60364-6 (measurements - verification)
IEC 60364-4-41 / HD 60364-4-41 (measurements – protection against
electric shock)
EN 04700 (measurements – acceptance tests)
EN 12464 (lighting of work places)
DIN VDE 0100
DIN VDE 0413
BS 7671
Sonel电气安全测量仪主要型号有:
MPI-530
MPI-525
MPI-520
MPI-505
MPI-502 -